TACSR 410mm2 Conduttore
TACSR 410mm2 Conduttore
TACSR 410mm2 Conduttore
TACSR 410mm2 Conduttore
TACSR 410mm2 Conduttore
TACSR 410mm2 Conduttore
TACSR 410mm2 Conduttore
TACSR 410mm2 Conduttore
TACSR 410mm2 Conduttore
TACSR 410mm2 Conduttore
TACSR 410mm2 Conduttore
TACSR 410mm2 Conduttore

1 / 5

TACSR 410mm2 Conduttore

Ottieni l'ultimo prezzo
Invia richiesta
Model No. : TACSR
Brand Name : HUAYUAN YONGTONG
Type : Bare
Conductor Type : Stranded
Application : Overhead
Conductor Material : Aluminum
Insulation Material : Bare
Material Shape : Round Wire
Certification : ISO9001
Brand : HUAYUAN YONGTONG
Di più
8yrs

Beijing, Beijing, China

Visita il negozio
  • Certificazione della piattaforma
  • video

Descrizione del prodotto

Specifica:

B.1 Technical Requirements

 

 

B.1.1 Technical Characteristics and Requirements

 

 

 

Owner's Requirement

Offered

a) Type

410 mm2 TACSR

410 mm2 TACSR

b) Code Word

N/A

N/A

c) Calculated total cross-sectional area, mm2

480.80 (approx.)

480.80 (approx.)

d) Outer Layers

 

 

1.Material

 Thermal Aluminum Zirconium Alloy (Al-Zir)

Thermal Aluminum Zirconium Alloy (Al-Zir)

2.Calculated Cross-sectional Area, mm2

413.40 (approx.)

413.40 (approx.)

3.Stranding No./dia. No./mm

26/4.5

26/4.5

4.Coefficient of Elongation (1°C) 1

 

23 × 10-6

e) Core

 

 

1.Material

Al. Clad Steel (AS)

Al. Clad Steel (AS)

2.Calculated Cross-sectional Area, (mm2)1

 

 

3.Stranding, No./Dia. No./mm

7/3.5

7/3.5

4.Zinc coating (Class/g/m2)

N/A

N/A

5.Coeff. Of Elongation (/°C) 1

 

13.0× 10-6

f) Conductor Overall Diameter, mm.

28.50 (approx.)

28.50 (approx.)

g) Rated Tensile Strength (RTS), kg

Not less than 13,910

 13910

h) Rated DC Resistance at 20°C, ohm/km 1

 

0.0694

i) Initial Modulus of Elasticity, (kg/mm2 )1

 

7700

j) Final Modulus of Elasticity, (kg/mm2) 1

 

7700

k) Percent Elongation at Rated Strength, % 1

 

 /

I) Permanent Elongation due to 10 year creep at 20% RTS 1

 

 /

m) Conductor Coeff. Of Linear Expansion (/°C) 1

 

18.9×10-6

B.1.2 Other Technical Requirements

 

 

a)Conductor lay, (Right, Left)

Right

Right

b)Length of Lay (Outer Layer) mm. 1

 

285--399(outside)

c)Corrosion Inhibitor (Grease) Required? (Yes, No)

No

No

d)Weight of Conductor (kg/km) 1

 

1587(approx)

e)Length Per Reel, m. 1

 

2000

B.1.3 Cable Reel

 

 

a) Material

Wooden2

Wooden drums with steel reinforced

b) Returnable, (Yes, No)

No

No

c) If yes, return within no. of months after installation

N/A

N/A

B.2 Tests and Experience Requirements

 

 

B.2.1 Test Requirements

 

 

 

Owner's Requirement

Offered

a) Stress-Strain Test and Report Required

Yes5

yes

b) Breaking Strength Test and Reports Required:

Yes6

yes

c)Factory Acceptance Tests (Routine Tests) to be witnessed by Owner's personnel.

No

No

d) Required no. of Owner's personnel to witness test

N/A

N/A 

Costruzione del conduttore:

Construction picture1

TACSR / AS 410 mm 2

Construction

Nominal NO./Diameter(mm)

Nominal Diameter(mm)

1--- Aluminum-Clad Steel Wire

7 / 3.50

10.50

2--- Aluminum Alloy Wire

26 / 4.50

28.50

Standard: IEC 61089; Filo di acciaio rivestito di alluminio standard: IEC 61232 20SA

Lega di alluminio filo standard: IEC 62004 AT1, max. temperatura operativa continua consentita 150 ℃.